Hai bisogno di un manuale per il tuo Seitron TAS02M Termostato? Di seguito è possibile visualizzare e scaricare gratuitamente il manuale in PDF in italiano. Questo prodotto ha attualmente 2 domande frequenti, 0 commenti e ha 1 voto con una valutazione media del prodotto di 0/100. Se questo non è il manuale che desideri, contattaci.

Il tuo prodotto è difettoso e il manuale non fornisce alcuna soluzione? Rivolgiti a un Repair Café per il servizio di riparazione gratuita.

Manuale

Loading…

TA S02M 0001 AN 022761C5 291013
OVERVIEW
This device is an electronic room thermostat for
heating systems suitable for reliable and accurate
temperature regulation in commercial and industrial
premises as well as for home installation.
The room temperature can be sensed by the internal
sensor or a remote sensor (optional).
OPERATION
When the measured room temperature is below the
value set on the dial the thermostat turns the relay on
and, at the same time, turns the red LED on.
SETTING THE ROOM TEMPERATURE
The user can set the room temperature by moving
the dial to any desired temperature, as explained in
the former paragraph, between 6°C and 30°C.
KNOB ROTATION LIMITATION
It is possible to limit the rotation range for the set-
poin knob by following these steps:
1. Remove the knob by tilting it, eventually with the help
of a screwdriver placed in the slot (2).
2. Pick up the plastic pins (4) parked at one side of
the knob area and set them (5) as in the example
of Fig. 6. In this example the rotation range (6) is
reduced as in the shown angle.
INSTALLATION
a
WARNING
- To adjust properly room temperature, install the
thermostat about 1.5m from floor level, far from
heat sources, airstreams or particularly cold
walls (thermal bridges). When the remote
sensor is used in conjunction with the
thermostat, then this note is to be applied to the
remote sensor itself.
- For remote version all wirings must be made
using wires with 1,5 mm² minimum cross
section and no longer than 25 m. Do not use
same duct for signal wires and mains.
- The appliance must be wired to the electric
mains through a switch capable of
disconnecting all poles in compliance with the
current safety standards and with a contact
separation of at least 3 mm in all poles.
- Installation and electrical wirings of this
appliance must be made by qualified
technicians and in compliance with the current
standards.
- Before wiring the appliance be sure to turn the
mains power off.
For installation the thermostat follow these steps:
1. Remove the knob by tilting it, eventually with the
help of a screwdriver placed in the slot.
2. Remove plastic cover by moving to the inner side,
through the use of a tool (Fig. 4), the two plastic
teeth (3) located on the left side (Fig. 3) of the
thermostat.
3. Fix the thermostat base plate to the wall through
the two screw holes with distance between axes of
60 mm.
4. Make the electrical connections, routing the wires
through the rectangular opening (8) and following
to the diagram of Fig. 4.
- ENGLISH -
3
5. Close the thermostat by carefully positioning the
cover so that the LED matches the relevant hole
and then by slightly pressing the cover in order to
make the four plastic teeth snapping. Then insert
the knob.
NIGHT SET BACK
In order to select the 'Night Set Back' feature an
external dry contact can be connected to terminal 6
(Fig. 5).
This mode results in reducing the temperature set
with the external dial by an amount set with the
internal trimmer (7) in Fig. 7, in the range 2°C .. 7°C.
The thermostat leaves the factory with the trimmer
set on 4.5°C.
SELECTION INTERNAL/EXTERNAL SENSOR
The thermostat leaves the factory configured by
default for operation with the internal temperature
sensor. If it is planned to install a remote sensor,
remove the jumper connector JP1 (8 of Fig. 7) and
connect an NTC type sensor (4700 ohm@ 25°C)
with a suitable beta value to terminals 7 and 8. In
case of doubt as to the type of sensor to connect,
please consult the manufacturer.
TECHNICAL FEATURES
Power supply:
TA S01M 0001: 230V~ -15% +10% 50Hz
TA S012 0001: 24V~ ±10% 50Hz
Power absorption:
TA S01M 0001: 5,3VA
TA S012 0001: 0,3VA
Regulation range: 6°C .. 30°C
Night set back: 2°C .. 7°C adjustable
(Default 4,5°C)
Differential: 0,5°C
Internal sensor type: NTC 4,7kΩ @ 25°C
Remote sensor optional: NTC 4,7kΩ @ 25°C
(optional)
Contact rating: 5 (1) A @ 250V~ SPDT
Protection grade: IP 30
Operating temperature: 0°C .. 40°C
Storage temperature: -10°C .. +50°C
Humidity limits: 20% .. 80% RH
(non condensing)
Case: Material: ABS self extinguishing V0
Color: Signal white (RAL 9003)
Size: 85 x 85 x 31 mm (W x H x D)
Weight: TA S01M 0001: ~135 gr.
TA S012 0001: ~ 130 gr.
NORMATIVE REFERENCES
The product complies with the following standards
(EEC 2004/108/c and 2006/95/c):
CEI-EN-60730-1 (2002)
CEI-EN-60730-2-9 (1998)
WARRANTY
The manufacturer is committed to the continual
development of its products and hence reserves the
right to change technical specifications and
performance features without notice. Consumers are
provided with a warranty against product non-
conformity in accordance with European Directive
1999/44/EC and the manufacturer’s guarantee policy.
The complete text of the warranty is available on
request from the seller.
Scarica il manuale in italiano (PDF, 0.18 MB)
(Rispetta l’ambiente e stampa questo manuale solo se è veramente necessario)

Loading…

Valutazione

Facci sapere che cosa pensi della Seitron TAS02M Termostato valutando il prodotto. Vuoi condividere la tua esperienze con questo prodotto o porre una domanda? Ti preghiamo di lasciare un commento al fondo della pagina.
Sei soddisfatto di Seitron TAS02M Termostato?
No
0%
100%
1 vota

Partecipa alla conversazione su questo prodotto

Qui puoi condividere cosa pensi di Seitron TAS02M Termostato. Se hai una domanda, leggi prima attentamente il manuale. La richiesta di un manuale può essere effettuata utilizzando il nostro modulo di contatto.

Maggiori informazioni su questo manuale

Comprendiamo che sia bello avere un manuale cartaceo per i tuoi Seitron TAS02M Termostato. Puoi sempre scaricare il manuale dal nostro sito web e stamparlo tu stesso. Se desideri avere un manuale originale, ti consigliamo di contattare Seitron. Potrebbero essere in grado di fornire un manuale originale. Stai cercando il manuale del tuo Seitron TAS02M Termostato in un'altra lingua? Scegli la tua lingua preferita sulla nostra home page e cerca il numero del modello per vedere se è disponibile.

Specifiche

Marca Seitron
Modello TAS02M
Categoria Termostati
Tipo di file PDF
Dimensione del file 0.18 MB

Tutti i manuali per Seitron Termostati
Altri manuali di Termostati

Domande frequenti su Seitron TAS02M Termostato

Il nostro team di supporto cerca informazioni utili sul prodotto e risposte alle domande più frequenti. Se trovi un’inesattezza nelle nostre domande frequenti, ti preghiamo di farcelo sapere utilizzando il nostro modulo di contatto.

Che cos’è la zona morta di un termostato? Verificato

Molti termostati moderni hanno una zona morta. Se la temperatura varia di meno di 4°C dalla temperatura impostata, il sistema non riscalda né rinfresca. Questa cosiddetta zona morta del termostato evita che il sistema si accenda e si spenga troppo frequentemente, risparmiando energia.

È stato utile (1592) Per saperne di più

Qual è il posto migliore per installare un termostato? Verificato

Il posto migliore per un termostato è circa a 1,5 metri dal pavimento. Non posizionare mai un termostato vicino a un radiatore o a un altro dispositivo che emette calore o alla luce diretta del sole. Scegliere una stanza che viene utilizzata di frequente. Nella maggior parte dei casi, la sala.

È stato utile (996) Per saperne di più
Manuale Seitron TAS02M Termostato

Prodotti correlati

Categorie correlate